Share by email

IEC 62021-3

IEC 62021-3:2014
Insulating liquids - Determination of acidity - Part 3: Test methods for non-mineral insulating oils
IEC 62021-3:2014 describes two procedures for the determination of the acidity of unused and used electrical non-mineral insulating oils. Method A is potentiometric titration and Method B is colourimetric titration. The method may be used to indicate relative changes that occur in non-mineral insulating oil during use under oxidizing conditions regardless of the colour or other properties of the resulting non-mineral oil. The acidity can be used in the quality control of unused non-mineral insulating oil. As a variety of oxidation products present in used non-mineral insulating oil contribute to acidity and these products vary widely in their corrosion properties, the test cannot be used to predict corrosiveness of non-mineral insulating oil under service conditions.
BASE PUBLICATION
  CHF 160.-

Technical committee

TC 10 Fluids for electrotechnical applications

Category

Environment - Quality Assurance - Safety
Publication typeInternational Standard
Publication date2014-03-19
Edition1.0
ICS

29.040.10

Stability date2030
ISBN number9782832214046
Pages50
File size1.36 MB
EditionDatePublicationEditionStatus